- Operated by a two position switch i.e. manually / automatically using a timer to change over from start to run position.
- In starting position supply is connected to stator windings through an auto-transformer which reduces applied voltage to 50, 60, and 70% of normal value depending on tapping used.
- Reduced voltage reduces current in motor windings with 50% tapping used motor current is halved and supply current will be half of the motor current. Thus starting current taken from supply will only be 25% of the taken by DOL starter.
- For an induction motor, torque T is developed by V2, thus on 50% tapping, torque at starting is only (0.5V)2 of the obtained by DOL starting. Hence 25% torque is produced.
- Starters used in lager industries, it is larger in size and expensive.
- Switching from start to run positions causing transient current, which can be greater in value than those obtained by DOL starting.
|